Shopping security
The ABB INICT03A functions as the high-speed communication gateway between the proprietary INFI-Net control network and supervisory host computers or Human-Machine Interfaces (HMI). Designed for the Symphony Harmony and INFI 90 Distributed Control Systems (DCS), this module handles massive data throughput with 2 Mbytes of RAM and an extensive 30,000-point tag capacity. It supports both standard RS-232-C serial links and high-speed SCSI interfaces, allowing real-time process monitoring and command execution with extreme reliability. We provide this unit as 100% Brand New and Original, ensuring seamless data availability for higher-level plant management systems.
| Parameter | Specification Details |
| Manufacturer | ABB Bailey |
| Model Number | INICT03A |
| Product Type | INFI-Net to Computer Transfer Module |
| Onboard Memory | 512 KB ROM; 2 MB RAM |
| Tag Capacity | 30,000 Point Definitions |
| High-Speed Interface | SCSI (Up to 4 Mbytes/sec) |
| Serial Interface | RS-232-C (Up to 19.2 kbaud) |
| Current Consumption | 2 A (Typical) / 10 W Power |
| Supply Voltage | +5 VDC (Backplane-supplied) |
| Operating Temperature | -20 °C to +60 °C (-4 °F to 140 °F) |
| Weight | 0.6 kg (Net) |
| Dimensions (WxHxD) | 5.1 cm x 17.8 cm x 33.0 cm |
Massive Database Support: The INICT03A manages up to 30,000 tag definitions within its 2MB RAM buffer. This high capacity enables operators to monitor entire plant sections through a single gateway, reducing the need for multiple interface modules and simplifying the DCS architecture.
High-Bandwidth Data Pipeline: The integrated SCSI interface supports transfer rates up to 4 Mbytes per second. This speed ensures that high-resolution trend data and critical system alarms reach the HMI instantly, preventing data bottlenecks during process upsets or heavy network traffic.
Dual-Interface Versatility: By offering both SCSI and RS-232-C ports, the module maintains compatibility with a wide range of host hardware. Use the SCSI port for high-speed server connections and the serial port for localized diagnostics or legacy terminal access without requiring additional converters.
Enhanced Thermal Design: Engineered to operate in environments from -20 °C to +60 °C, the INICT03A withstands the fluctuating temperatures typical of industrial control rooms. This thermal resilience prevents hardware-induced communication timeouts and extends the operational life of the internal components.
What is the difference between the INICT03 and the INICT03A?
The INICT03A offers significantly expanded memory and processing capabilities compared to earlier revisions. Specifically, the 2MB RAM and the ability to handle 30,000 tags make it the preferred choice for modern plant upgrades where high data density is required.
Can I replace an older computer interface module with an INICT03A?
Yes. The INICT03A serves as a direct replacement for several legacy INFI 90 computer interface modules. However, ensure your host computer drivers and the specific HMI software (such as Composer or Conductor) support the expanded tag capacity and SCSI communication protocols.
Does this module require a separate termination unit for SCSI connections?
Yes. The INICT03A typically works in conjunction with a termination unit (such as the NTMP01) to provide the physical SCSI and RS-232-C ports. The module slides into the rack and interfaces with the termination unit through the backplane connectors.
How does the 30,000 tag capacity benefit plant operations?
A higher tag capacity allows the DCS to export more detailed internal variables—such as PID tuning parameters, diagnostic statuses, and secondary sensor data—to the supervisory system. This visibility enables better data analytics and more informed decision-making for plant engineers.